Earthing Conductor Size Calculator | Calculate Grounding Wire Size

    Created by Md jony islam

    Earthing Conductor Size Conversion Calculator

    The Earthing Conductor Size Calculator helps determine the proper size of grounding conductors based on factors like fault current, voltage, and safety requirements for electrical systems. An earth conductor size calculator serves as a necessary instrument that determines appropriate grounding conductor sizes in electrical systems. The PE (Sqmm) calculation determines the earthing conductor minimum cross-sectional area through √ (Ifault2 × t) / k. Earth grounding conductors correctly selected for their dimensions create safety zones for electrical systems, thus protecting against faults while minimizing both heat generation along with the potential threat of fire emergencies and electric shock hazards. The calculator forms an essential part for creating safe and dependable grounding systems that serve residential, commercial, and industrial purposes.

    Earthing Conductor Size Calculator

    Earthing Conductor Size Calculator
    A
    Sec
    sqmm

    Learn how we tools this below

    Add this tools to your site

    Buy me a for Source Code

    What do you need to know to calculate Earthing Conductor Size?

    🙋 Try our Va To Kw Calculator . If you want to learn more about conversions using Electrical Engineering Project Calculators.

    Conversion using the Earthing Conductor Size Calculation Formula

    PE(Sqmm) = Ifault × √tK

      Where:

    • PE = Minimum cross-sectional area of the earthing conductor (in mm²)
    • Ifault = Fault current (in amperes, A)
    • t = Duration of the fault (in seconds, s)
    • K = A constant that depends on the material used for the conductor (for copper, k ≈ 115; for aluminum, k ≈ 85)

    How to Explanation Earthing Conductor Size Calculator?

    Earthing Conductor Size conversion chart

    Fault Current (Ifault) (A)Fault Duration (t) (s)Material Constant (k)Earthing Conductor Size (PE) (Sqmm)
    5000.51155.72
    8001.01158.49
    10001.58511.48
    12002.08514.80

    Earthing Conductor Electrical Properties chart

    MaterialElectrical Resistivity (Ω·m)Electrical Conductivity (% IACS)
    1.68 × 10-8 Ω·m100%
    2.82 × 10-8 Ω·m61%
    1.00 × 10-7 Ω·m~15%

    Frequently Asked Questions - Earth Conductor Size Calculate Conversion FAQs:

    How do you calculate the minimum earth conductor size?

    To determine earth conductor dimension, you need to apply the formula Earth Conductor Size = k × √(I² × t), using k as the conductor constant, I for fault current, and t for fault clearance time. Based on copper material (k=143) properties and a 1000 A fault current along with a 1 s clearing time, the minimum size required becomes 4.52mm².

    What is the relationship between fault current and earth conductor size?

    The size requirement for Earth conductors is determined from the square root value of existing fault currents. The proportional relationship ensures the earth conductor maintains enough thermal capacity as a safeguard in case of faults. The area of conductors increases in direct proportion to the level of fault current they need to handle.

    How do you determine earth conductor size based on main conductor?

    Section 2.5 shows the calculations for determining earth conductor size, which should equal 50% of the main phase conductor size for 35mm² and under but 25% for 35mm² and larger sizes. The minimum required earth conductor measurement for a 50mm² main conductor amounts to 12.5mm².

    Why is proper earth conductor sizing important for electrical safety?

    Size determination leads to efficient fault current management that protects conductors from overheating and promotes safety during ground faults. Electrical safety of personnel and equipment depends on this practice.

    How do you calculate voltage drop in earth conductors?

    The formula to determine voltage drop requires calculation as V = I × L × ρ / A, with I being current, L length, ρ resistivity, and A representing conductor area. The calculation enables verification of Earth fault loop impedance staying in the safe operating zone.

    About the Author

    Md Jony Islam

    Md Jony Islam: Multidisciplinary Engineer & Financial Expert:

    Md. Jony Islam is a highly skilled professional with expertise in electronics, electrical, mechanical, and civil engineering, as well as finance. Specializing in transformer service and maintenance for 33/11kV substations, he ensures reliable and efficient electrical systems. His mechanical engineering skills drive innovative designs, while his financial acumen supports effective project budgeting. With a strong foundation in civil engineering, he contributes to robust infrastructure development. Md. Jony Islam's multidisciplinary approach ensures efficiency, quality, and reliability across all projects.