AC & DC Busbar: Key Differences and Considerations
The distribution and power collection of electrical energy occurs through busbars, as these serve as electrical conductors. The main concepts of busbar construction stay consistent for AC and DC systems, but their implementation varies according to electricity type.
Step-by-Step Process for Busbar Sizing:
For copper busbar: Iccc = 1.2 × busbar width × Bus Bar thickness
For silver steel busbar: Iccc = 1.6 × busbar width × Bus Bar thickness
For aluminum busbar: Iccc = 0.8 × busbar width × Bus Bar thickness
For iron busbar: Iccc = 0.6 × busbar width × Bus Bar thickness
For galvanized steel busbar: Iccc = 0.6 × busbar width × Bus Bar thickness
When load is given:
For DC circuit:
The formula for DC circuits is given below.
For Single Phase AC Circuit:
The formula for single phase AC circuit is same as DC with an additon for power factor (pf) which is given as:
For 3 phase AC circuits Line to Line:
The formula for a three-phase AC circuit matches the formula of two phase AC circuit with the inclusion of the factor square root 3 (~1.73) in line to line (Vll) voltage evaluations.
For 3 phase AC circuits Line to neutral:
When voltage is expressed in terms of line to neutral then we use 3 instead of 1.73.
Suggested Reading
- Ripple Voltage Conversion Calculator
- Fusing Current Conversion Calculator
- Rms Voltage Conversion Calculator
- Full Load Current Turns Ratio Conversion Calculator For Transformer
- Extruder Power Conversion Calculator
- Charge To Current Conversion Calculator
- Kva To Watts Conversion Calculator
- Wheel Horsepower Conversion Calculator
- Peak Voltage Conversion Calculator
- Rpm To Voltage Conversion Calculator
- Pulsed Laser Average Power Conversion Calculator
- Kva To Va Conversion Calculator
- Current To Energy Conversion Calculator
- Full Load Current Conversion Calculator
- Average Power Conversion Calculator
- 3 Phase Power Conversion Calculator
- Received Power Conversion Calculator
- Speed To Power Conversion Calculator
📌 Key Differences Between AC and DC Busbars
Factor | AC Busbar | DC Busbar |
---|---|---|
Current Type | Alternating Current (AC) | Direct Current (DC) |
Voltage Fluctuations | Voltage varies in cycles (sinusoidal) | Constant voltage with no fluctuations |
Design Considerations | Need to account for skin effect (current flows more on the surface of the conductor at high frequencies) | No skin effect; current flows uniformly through the conductor |
Material Selection | Usually copper or aluminum | Similar, but may consider higher conductivity materials for DC systems |
Insulation | Typically used with higher-rated insulation due to voltage peaks (especially for high-frequency AC) | DC busbars often need greater insulation thickness for high-voltage systems |
Short-Circuit Considerations | AC busbars are designed to handle alternating fault currents which can vary | DC busbars are designed to handle constant fault currents, which can be harder to interrupt |
Size | AC busbars tend to be smaller than DC busbars of the same rating due to skin effect | DC busbars may need larger cross-sectional areas to handle the continuous current |
Typical Safety Factors for Busbars
Application | Safety Factor (S.F.) |
---|---|
General Industrial Use | 1.25 - 1.5 |
Critical Power Systems | 1.5 - 2.0 |
High-Temperature Environments | 1.5 - 2.0 |
Short-Circuit Withstand Design | 2.0 - 2.5 |
👉 Formula:
🔹 Rated Ampacity = Required Load × Safety Factor
Busbar Ampacity Per Square mm chart
Material | Ampacity (A/mm²) |
---|---|
Silver (Ag) | 1.6 - 2.0 |
Copper (Cu) | 1.2 - 1.6 |
Aluminum (Al) | 0.7 - 1.0 |
Steel (Mild/SS) | 0.1 - 0.3 |
Iron (Fe) | 0.1 - 0.2 |
Galvanized Steel | 0.15 - 0.25 |
- Silver: has the highest conductivity, but it's rarely used due to cost.
- Copper: is commonly used in electrical systems due to its high ampacity.
- Aluminum is lighter and cheaper but has lower ampacity than copper.
- Steel, Iron, and Galvanized Steel have much lower conductivity and are not ideal for high-current applications.
Where:
Frequently Asked Questions - Bus Bar Size Conversion FAQs:
The correct determination of busbar width and ampacity stands essential for providing reliable, safe electrical power distribution. The method examines copper and aluminum materials in addition to current rating and ambient temperature alongside voltage drop to guarantee safe power distribution and overload protection capabilities.
Sizing a busbar requires determination of its safety factor between 1.25 and 1.5 because it enables handling unexpected overloads or short-circuit conditions. The additional factor allows the busbar to maintain operational safety during regular operation and short-circuit events.
The required ampacity in amperes allows us to determine the cross-sectional area through division by the material ampacity per unit area, such as copper at 1.2 A/mm². The formula is:
This ensures the busbar can safely carry the required continuous current.
The necessary selection process depends on four main elements, including busbar rating and material selection between copper and aluminum, along with environmental temperature conditions as well as circuit busbar length and voltage definition combined with safety factor requirements. The factors determining heat dissipation and ampacity together affect the entire performance of electric busbars in power distribution circuits.
The voltage drop is calculated using the formula:
The relationship applies the current value I to the busbar resistance R_busbar. Power distribution efficiency relies on this calculation to maintain an acceptable voltage drop across the busbar.