3-Phase Power Calculator | Calculate Power in Three-Phase Systems

    Created by Md jony islam

    3-Phase Power Conversion Calculator

    Use our 3-Phase Power Calculator to determine real, apparent, and reactive power in three-phase electrical systems based on voltage, current, and power factor. A 3-Phase Power Calculator functions as a time-saving instrument to determine three-phase power usage by processing real power (kW), apparent power (kVA), and reactive power (kVAR). Users can simplify complex electrical calculations by entering voltage and current and power factor values to obtain automatic solution results through this tool. The power calculation formula requires P equals √3 * V * I * PF where P stands for power in kilowatts (kW) and V represents voltage strength and I represents current flow strength, while PF identifies power factor. The tool functions as an essential instrument which professionals in engineering, electricity, and technical fields use for power system optimization as well as electrical load control.

    3 Phase System Power Calculator

    3 Phase Power Calculator
    V
    A
    pf
    KW
    KVA
    KVAr

    Learn how we tools this below

    Add this tools to your site

    Buy me a for Source Code

    What do you need to know to calculate 3-Phase Power?

    🙋 Try our Motor Efficiency Calculator . If you want to learn more about conversions using Electrical Engineering Project Calculators.

    Conversion using the 3 Phase Power Calculation Formula

    Formula to Calculate the Active Power:

    Active Power (KW) = (√3 × Voltage (V) × Current (I) × Power factor)1000

    Formula to Calculate the Apparent Power:

    Apparent Power (KVA) = (√3 × Voltage (V) × Current (I))1000

    Formula to Calculate the Reactive Power:

    Reactive Power (KVAr) = √[(KVA)2 - (KW)2]

      Where:

    • √3 = A constant for 3-phase systems (approximately 1.732).
    • Voltage (V): = The line-to-line voltage in volts.
    • Current (A): = The current in amperes.
    • Power Factor: = The ratio of real power to apparent power (a value between 0 and 1).
    • Cosθ = Power factor in AC circuits
    • KVA = Kilovolt-Ampere
    • KVAr = Kilovolt-Ampere Reactive
    • 1000 = Converts the result from watts to kilowatts.

    Key Differences:

    3-Phase Power conversion chart

    Input Voltage (V)Input Current (A)Power Factor (PF)Active Power (kW)Apparent Power (kVA)Reactive Power (kVAR)
    230100.83.193.982.39
    400200.912.4713.855.99
    415300.8518.3121.529.91
    440500.9536.1938.0812.33
    480750.956.0362.2724.68
    6001000.8588.19103.9255.74

    Frequently Asked Questions - 3-phase Power Calculate Conversion FAQs:

    How do you calculate three-phase power?

    The calculation for three-phase power requires the P = √3 × VL × IL × PF formula, which uses P as power in watts, VL as line voltage, IL as line current, and PF as power factor. The system, which operates at 400 V and 25 A and 0.85 PF, generates a power output of 14.7 kW.

    What is the relationship between line and phase values in three-phase systems?

    The ratio for line voltage to phase voltage when using a delta connection is √3, and line current to phase current is √3 when using a wye connection. The relationship between three-phase power calculations needs accurate results.

    How do you calculate three-phase apparent power (kVA)?

    To determine apparent power, measure S = √3 × VL × IL, where power factor should not be included. The apparent power output of a system operating at 400 V and 25 A amounts to 17.3 kVA. The calculated values serve to evaluate total system capacity.

    Why is power factor important in three-phase calculations?

    Actual power consumption relies on power factor to show its relation to apparent power. Less than half (80%) of the apparent power transforms into useful work when the power factor stands at 0.8. The power efficiency and utility expenses suffer when such conditions prevail.

    How do you determine reactive power in three-phase systems?

    You can determine reactive power by multiplying actual power P with tan(arccos(PF)) to yield results in VAR. System power factor and efficiency assessment can be done through this calculation.

    About the Author

    Md Jony Islam

    Md Jony Islam: Multidisciplinary Engineer & Financial Expert:

    Md. Jony Islam is a highly skilled professional with expertise in electronics, electrical, mechanical, and civil engineering, as well as finance. Specializing in transformer service and maintenance for 33/11kV substations, he ensures reliable and efficient electrical systems. His mechanical engineering skills drive innovative designs, while his financial acumen supports effective project budgeting. With a strong foundation in civil engineering, he contributes to robust infrastructure development. Md. Jony Islam's multidisciplinary approach ensures efficiency, quality, and reliability across all projects.