    3 Phase Load Conversion Calculator

    Easily calculate 3-phase load in kW, kVA, and Amps using voltage & power factor. Perfect for electrical sizing, generator selection, and power system analysis. A 3-phase load calculation depends on three vital electrical factors, which include voltage (V), current (A) and power factor (PF). The electricity system has two operating states either equal forces spread across all three phases or different loads present between the phases. Precise analysis of these system factors leads to proper distribution of power and correct generator sizing and operational efficiency. The process of determining 3-phase load correctly enables engineers to select transformers and generators along with circuit protectors, which leads to enhanced energy consumption while avoiding system overload incidents. Load analysis precision provides multiple benefits to operational systems and their operating time span. It optimizes transformer selection and supports generator and circuit breaker installation decisions, as well as power efficiency and equipment overload prevention.

    3 Phase Load Calculator

    🏠 3 Phase Load Calculator
    Add Load

    Learn how we tools this below

    Add this tools to your site

    Buy me a for Source Code

    What do you need to know to calculate 3 Phase Load?

    🙋 Try our Series Current Calculator . If you want to learn more about conversions using Electrical Engineering Project Calculators.

    Conversion using the 3 Phase Load Formula:

    To convert and calculate your 3 phase total power consumption in watts, use the Home Load Formula:

    Total Power (W) = 3 × Voltage (V) × Current (A) × Power Factor (PF)

    For Example, 3 phase Load Calculation given data: Voltage = 230V (standard single-phase supply). Appliances: Led bulb = 10w × 5 = 50W, Ceiling Fan = 75w × 2 = 150W, Refrigerator = 150W, Washing Machine = 500W, Air Conditioner = 1200W.
    Step-by-step Calculation:
    Total Power Consumption (W):


    Total Power(W) = 50W + 150W + 500W + 1200W = 2050W ≈ 2.05kw.
    Current(A) = Total Power (W)3 × Voltage × Power factor
    Current(A) = 2050W3 × 400V × 0.9

    Total Load = 2050W (2.05kw).
    Estimated Current Draw = 3.29A.
    To ensure safety and prevent overheating, multiply by 1.25 (25% safety margin): Breaker Rating = 3.29 × 1.25 = 4.11A.

    How to Use a 3 Phase Load Calculator

    A 3 Phase Load Calculator helps estimate your total power consumption and electrical load capacity. Follow these steps:

    Step 1 - Enter Voltage: Select your power supply voltage (e.g., 230V for single-phase or 415V for three-phase).

    Step 2 - List Appliances: Enter the wattage (W) or power rating of each electrical device (e.g., bulbs, fans, refrigerator, AC). If wattage is unknown, use: Power (w) = Voltage (v) × Current (A).

    Step 3 - Enter Quantity and Usage Hours: Input the number of each appliance. Specify daily usage hours for energy estimation.

    Step 4 - Calculate Total Load: The calculator sums all appliance wattages: Total Load = ∑(Wattage × Quantity).

    Step 5 - Power Factor (For AC Load): If applicable, enter power factor (PF) (typically 0.8 - 0.9 for household loads). Adjusted formula: Real Power (W) = Voltage × Current × PF

    Step 6 - View Results: The calculator provides total power (W), estimated current (A), and recommended circuit capacity. Use this data for proper wiring, circuit breaker selection, and generator sizing.

    Step 7 - Apply Safety Factor: To ensure safety and prevent overheating, multiply by 1.25 (25% safety margin): Breaker Rating = 10.87A × 1.25 = 13.58A

    Choose the Next Standard Breaker Size: Circuit breakers come in standard sizes such as 6A, 10A, 16A, 20A, 25A, etc. Since 13.58A is not a standard rating, choose the next higher standard size:

    3 phase Load Conversion Chart

    kWkVA (PF 0.8)Current (A) at 400VCurrent (A) at 415VCurrent (A) at 480V
    1012.518.117.415.1
    202536.134.830.1
    5062.590.28775.2
    100125180.4174.1150.3
    200250360.8348.2300.7
    500625902870.4751.8

    Frequently Asked Questions - 3 Phase Load Conversion FAQs:

    What is a 3-phase load calculation?

    A 3-phase load calculation determines power (kW, kVA) and current (A) in a 3-phase system using voltage and power factor. It helps in system design and equipment sizing.

    How do you calculate 3-phase power in kW?

    Use the formula:

    KW = √3 × V × I × pf1000

    where V = voltage, I = current, PF = power factor.

    How do I determine the current in a 3-phase system?

    Current (A) is calculated as:

    I = KW√3 × V × PF
    What is the difference between kW and kVA?

    kW (real power) is the actual power consumed, while kVA (apparent power) includes both real and reactive power, calculated as kW ÷ PF.

    Why is power factor important in 3-phase systems?

    Power factor affects real power efficiency. A low PF increases current draw, leading to energy losses and higher costs.

    About the Author

    Md Jony Islam

    Md Jony Islam: Multidisciplinary Engineer & Financial Expert:

    Md. Jony Islam is a highly skilled professional with expertise in electronics, electrical, mechanical, and civil engineering, as well as finance. Specializing in transformer service and maintenance for 33/11kV substations, he ensures reliable and efficient electrical systems. His mechanical engineering skills drive innovative designs, while his financial acumen supports effective project budgeting. With a strong foundation in civil engineering, he contributes to robust infrastructure development. Md. Jony Islam's multidisciplinary approach ensures efficiency, quality, and reliability across all projects.